español

Single-phase protector / measuring apparatus DOV 842

Presented in casing for Standard DIN 35mm rail (EN 50 022), it is a compact device controlled by a 16 Bit microcomputer, highly stable due to the inclusion of a double state of process watchdog. It withstands permanent and transitory peak surges, as well as low voltage. It can protect multiple, single-phase or three-phase lines, of up to 63A.
It provides diverse measurements and protections programmable in value and delay :

  • Differential protection with very high speed cut-off
  • Protection against peak surge via very high speed physical cut-off
  • Protection against low voltage
  • Protection against over-intensity
  • True RMS and Peak Measurement of V, I, I ∆ n, W, VA, VarL, VarC, kWh, Etc.

Moreover, constant surveillance of the power input enables an Intelligent Automatic Reset (conditioned). In other words, it resets only on re-establishing normality in the supply. Certain models / versions have Remote Control input and output.

 

Single-phase protector / measuring apparatus (2 poles) With I. Differential
MODEL DOV
VERSION 842

True RMS and Peak Voltage Measurement

0V to 1000Vpk ·

True RMS and Peak Voltage Measurement

0V to 500Vpk

 

True RMS Intensity and Peak Measurement in autoscale

0A to 20Apk & 0A to 100Apk  

Differential Intensity True RMS and Peak Measurement

0mA at 500mApk ·

Active Power (W) and Apparent Power (VA) Measurement

4 quadrants Resolution 0.1W, 0.1VA  

Inductive Reactive Power Measurement

4 quadrants Resolution 0.1VArL  

Capacitive Reactive Power Measurement

4 quadrants Resolution 0.1VArC  

Power Factor and Line frequency Measurement of:

0.001 to 1
10.00Hz to 100Hz

 

Active Energy Counter in Real Time

000000.00001 kWh to 999999.99999 kWh + 9-lap counter

 
Reactive Energy Counter in Real Time

000000.00001 kWh to 999999.99999 kWh + 9-lap counter

 

Protection due to Peak Surge value and delay programmable

True RMS
Peak

245V to 275V & 20mS to 5Seg
350Vpk to 400Vpk & 0.3mS to 5mS

·

Protection due to Low Voltage value and delay programmable

True RMS 175V to 200V & 20mS to 5Seg ·

Protection due to Over Intensity value and delay programmable (DISABLING)

True RMS
Peak

5A to 60A & 20mS to 10Seg
7Apk to 84Apk & 0.3mS to 5mS

 

Protection due to Differential Intensity I D n value and delay programmable

True RMS
Peak
5mA to 30mA & 20mS to 160mS
7mApk to 42mApk & 0.3mS to 5mS
·

Protection due to Differential Intensity I D n value and delay programmable

True RMS
Pico

50mA to 300mA & 20mS to 160mS
70mApk to 420mApk & 0.3mS to 5mS

 

Independent Programmable Resets due to Differential intensity

0 to 10 resets and 3 to 240 minutes each one ·

Independent Programmable Resets due to Peak Surge

0 to 10 resets and 3 to 240 minutes each one

 

Independent Programmable Resets due to Circuit breakers

0 to 10 resets and 3 to 240 minutes each one

·

Real Incremental Protection Test:

I D n Differential

·

Real Incremental Protection Test:

Peak Surge

·

Real Incremental Protection Test:

Low Voltage

·

Real Incremental Protection Test:

Over-Intensity

 

Self-testing of Differential + Toroidal Transformer sensor

·

Self-testing of outer cabling, internal electronic system

·

Chronological recorder of incidents and protections of all the alarms (Value, Tour, Minute, Day, Month, Year)

 

Totaliser – Counter of cut-off time due to power failure

 

Independent cut-off counters of all the alarms + accumulated total and historical total

·

Alarm register and their history (Maximum and minimum values)

·

Register of maximum measurements

·

Programmable Start-up delay  0 to 999 sec.

·

Manual Cut-off (Reset only with user key code)

·

Security settings (Programming of all the parameters only with user key code)

·

Average measurement displayed, programmable from 20 Ms to 1000 Ms

·

Change of user key code

·

Setting by default of Alarms (Value and Delay)

·

Automatic / Manual Display / Manual (Data rotation)

·

Programmable Calendar Clock

 

“Info” function (Information about the state of the alarm programming)

·

Acoustic and luminous indicator

·

 

 

 

 


Download PDF
Download this manual
in PDF format.
(requires Acrobat Reader)